Working Principle?
The device operates on a thermal measurement principle. Its sealed probe contains two resistors:
Heated resistor?: Serves as the sensing element.
Reference resistor?: Maintains ambient temperature.
When fluid flows, heat dissipation from the heated resistor alters its resistance value. The differential resistance between the two resistors determines the flow velocity.
Key Features?
Maintenance-free?: No moving parts.
Universal installation?: Single model accommodates multiple pipe diameters.
Low pressure loss?.
Integrated functions?:
Color LCD displays flow trend and switch status.
Built-in temperature measurement with alarm and remote monitoring capabilities.
Applications?
Media compatibility?: Liquids (water, oil), gases, and gas-liquid mixtures.
Typical uses?:
Low-flow alarms.
Pneumatic/hydraulic systems.
Coolant/lubricant flow monitoring.
Pump dry-run protection.
Technical Parameters?
Category Specifications
Flow Range? 0.01–2.0 m/s (water)
Temperature Range? 0–100°C (medium) / -20–80°C (ambient/storage)
Temperature Accuracy? ±1.5°C (when probe is immersed)
Output Signals? ?Temperature?: PNP/NPN/IO-link, 4–20mA, 1–5V
?Flow?: PNP/NPN/IO-link, 4–20mA, 1–5V
Power Supply? 24V DC ±20%
Current? Max. 200mA (PNP/NPN), Consumption <100mA
Display? 0.96" color LCD (flow/temperature)
Configuration? Button-operated settings
Pressure Rating? 100 bar
Response Time? 1–13s (typically 2s)
Electrical Protection? Reverse polarity, short-circuit, overload protection
IP Rating? IP67
Materials? ?Housing?: Stainless steel/engineering plastic
?Wetted parts?: 316L stainless steel/EPDM
Connector? M12 plug